World Geothermal Congress · 29. Geothermal Heat Pumps
An Absorption Refrigeration System Used for Exploiting Mid-Low Temperature Geothermal Resource
Abstract
An absorption refrigeration system used for exploiting mid-low temperature geothermal resources is described, in which a two-stage LiBr/H2O absorption chiller driven by hot water is the core technique. The refrigeration system is driven by a low-temperature hot source and consists of an evaporator, a low-pressure absorber, a low-pressure generator, a high-pressure absorber, a high-pressure generator, a condenser, a low-pressure heat exchanger, and a high-pressure heat exchanger.This refrigeration system can reduce the geothermal water of above 70C to 60C. Experimental data indicated that the COP of this chiller ranges from 0.38 to 0.42 with heat source temperature of 63-65C. Compared to the traditional air-conditioner, implementation of this system reduces power consumption by 62%, and the payback period of the investment is less than four years. This system has a high value of practice and a great deal of market prospect.
Details
Suggested citation
Wei-bin Ma, Chao Luo,Yu-lie Gong (2010). An Absorption Refrigeration System Used for Exploiting Mid-Low Temperature Geothermal Resource. Proceedings, World Geothermal Congress 2010, Paper 2911.
Proceedings-level reference. Individual papers do not carry DOIs.