World Geothermal Congress · Power Generation

Wayang Windu Integrated Control System - The Control Concept for Modern Geothermal Plant?

Pero Skoric, Reid Boutot, John Scott and Akira Iwata

Abstract

An Integrated Control System for geothermal plant is a new control and operation concept. The system is applied for the first time on Wayang Windu Geothermal Project. The system objectives, design concept and the hardware environment are presented. The main objective of the system is to integrate the steamfield and the station through a common operation and control philosophy. This enables the plant to operate automatically at its nominal electrical output for the total operation time, at the same time keeping the separation pressure stable with no steam venting during normal operation. The system is designed as a software package running within the project DCS. It controls the turbo generator by operating the turbine control valves through the governor. On the steamfield side the system operates remotely operable wellhead valves that particular wells are equipped with. A dynamic model of the project has been designed and implemented during the factory acceptance test. At present the system that controls one unit and the steamfield has been partially commissioned. However, the system has been designed to enable more units to operate as a set. An Integrated Control System, although developed for a new project, could easily be implemented on existing geothermal plants.

Details

Conference
World Geothermal Congress
Year
2000
Session
Power Generation (43 papers)
Paper number
R0282
Language
English
Geographic area
Wayang Windu, Indonesia; Java
Copyright
International Geothermal Association
Keywords
geothermal Wayang Windu Indonesia control steamfield power station integrated operation
Record ID
3963

Suggested citation

Pero Skoric, Reid Boutot, John Scott and Akira Iwata (2000). Wayang Windu Integrated Control System - The Control Concept for Modern Geothermal Plant?. Proceedings, World Geothermal Congress 2000, Paper R0282.

Proceedings-level reference. Individual papers do not carry DOIs.

More papers by Skoric ›