Asian Geothermal Symposium

Development of Ground-Source Heat Pump System Using a Flowing Well

Gaurav Shrestha, Youhei Uchida, Satoru Kuronuma, Mutsumi Yamaya, Masahiko Katsuragi

Download PDF (1MB)

Abstract

For the promotion of ground-source heat pump (GSHP) system in Japan, development of highly efficient system is essential. In this study, GSHP system was developed using a flowing well as a ground heat exchanger (GHE). Flowing well of 250mm diameter and 100m depth was constructed. Slit screens were set at intervals of 61.45 m - 83.45 m and 88.95 m - 99.95 m. 3 sets of 100m double U-tube with 34mm external diameter were installed and connected to 3 heat pumps of 10kW capacity. Performance of the system was evaluated for space-heating and space-cooling of an office building with room area of 126.7 sq. m. Average coefficient of performance (COP) was 4.5 for space-heating and 8.1 for space-cooling. Maximum heat exchange rate was 70.8 W/m for space-heating and 57.6 W/m for space-cooling. It can be said from these data that the system resulted in higher performance. Energy saving and cost reduction can be expected from this kind of system.

Details

Conference
Asian Geothermal Symposium
Year
2016
Language
English
Geographic area
Japan
Copyright
Asian Geothermal Symposium
Keywords
ground-source heat pump system flowing well performance Japan
Record ID
27655

Suggested citation

Gaurav Shrestha, Youhei Uchida, Satoru Kuronuma, Mutsumi Yamaya, Masahiko Katsuragi (2016). Development of Ground-Source Heat Pump System Using a Flowing Well. Proceedings, Asian Geothermal Symposium 2016.

Proceedings-level reference. Individual papers do not carry DOIs.