Stanford Geothermal Workshop · Direct Use

Numerical Modeling of Slinky-coil Horizontal Ground Heat Exchangers with Snow-covered Ground Surface

Hikari FUJII, Shohei YAMASAKI, Takahiro MAEHARA

Download PDF (358 KB) Hosted on pangea.stanford.edu

Abstract

In geothermal heat pump systems, the use of Slinky-coil horizontal ground heat exchangers (HGHEs) remarkably reduces the initial cost of the systems since the HGHEs can be constructed without using drilling machines. Hence, the HGHEs have been widely used mainly in northern America for heating and cooling purposes. The performance of the Slinky-coils, however, had not been successfully predicted with good accuracy since the complicated shape of the Slinky-coils made the modeling quite troublesome. To enable this, Fujii et al. (2012) developed numerical models of Slinky-coils using simplified grid systems with an FEM based software, FEFLOW. Then, they demonstrated the validity of the models through the history matching between field test and numerical results. In the numerical modeling, the consideration to energy balance at ground surface was found to be important since the horizontal GHEs are buried in shallow ground, less than 2 m deep. In Fujii et al. (2012), the accuracy of the modeling approach was proved for GHEs located in a warm region of Japan, where no snow accumulation is observed in winter. To promote the application of the system, it is important to accommodate the model to be used under any type of climate. For this target, we carried out field tests of Slinky-coil GHEs in Aomori Prefecture of Japan, where snow depth could exceed 1 meter in winter, and obtained ground temperature and heat medium temperatures. The numerical model was then modified to be able to evaluate the near surface temperatures with snow coverage. Reasonably good history matching results were obtained between measured and numerical temperatures demonstrating the validity of the model in cold regions.

Details

Conference
Stanford Geothermal Workshop
Year
2013
Session
Direct Use
Paper number
Fujii
Language
English
Geographic area
Hirakawa City, Japan
Copyright
Stanford Geothermal Program
Keywords
heat pump Slinky-coil numerical modeling
Record ID
19032

Suggested citation

Hikari FUJII, Shohei YAMASAKI, Takahiro MAEHARA (2013). Numerical Modeling of Slinky-coil Horizontal Ground Heat Exchangers with Snow-covered Ground Surface. Proceedings, Stanford Geothermal Workshop 2013, Paper Fujii.

Proceedings-level reference. Individual papers do not carry DOIs.

More papers by Fujii ›